Instructions Manual
R-MI-XT5 Rev.: 2 English version
XT5 /XT5H
Converter for
Flomid/Flomat
Sensors
instrumentation
for fluids
Vue de la page 0
1 2 3 4 5 6 ... 23 24

Résumé du contenu

Page 1 - Instructions Manual

Instructions Manual R-MI-XT5 Rev.: 2 English version XT5 /XT5H Converter for Flomid/Flomat Sensors instrumentation for fluids

Page 2

10 In the case of using a par-pos cable, which has two shielded pairs of cables (one for the electrodes and one for the coils) there is only one shiel

Page 3

11 3.1.3 Nominal diameter In this screen the nominal diameter (internal diameter) in millimetres of the sensor, or the pipe size in the case of a Flom

Page 4

In the first screen the flow rate for the 4 mA point (lower range) is configured. In the next screen the flow rate for the 20 mA point (upper range) i

Page 5 - - mA (negative)

3.2.3 Pulse output In this screen, there are two options. a) Frequency output (Hz). This is meant for transmitting the instantaneous flow rate to a

Page 6

14 Only the flow rate indication of the display and the analog output are affected by the filter. The pulse output and the totalizer act according to

Page 7

In an XT5H converter, if during a configuration sequence a HARTTM command, which should be attended, is received, the local configuration sequence wi

Page 8 - Terminal

In order to see the software version and return to the normal working screen, touch any key. 3.5 Empty pipe indication When the XT5 detects that the

Page 9

Summary of the principal communication characteristics: 17 Manufacturer, Model and Revision Tecfluid S.A., XT5 converter, Rev. 1 Device type Transm

Page 10

7 MAINTENANCE No special maintenance is required . For cleaning, a humid cloth can be used, and if necessary with a little soap. Solvents or other ag

Page 11

9 TECHNICAL CHARACTERISTICS 9.1 Power supply 230, 240, 115, 24 VAC 50, 60 Hz . 24 VDC. Power consumption: ≤ 5 VA 9.2 Analog output 4-20 mA. Active

Page 12

INDICE 1. INTRODUCTION ... 4 2. ELECTRICAL CONNECTON ...

Page 13

10 DIMENSIONS COMPACT MODEL WALL MOUNTING MODEL 20

Page 14 - Average flow rate

11 TROUBLESHOOTING Problem Probable cause Remedy The flow rate is not displayed. In its place there are dashes The pipe is empty. Make sure that th

Page 15

12 PROGRAMMING DIAGRAM Problem Probable cause Remedy The display is blank Fused fuse. Change the fuse. The analog output gives always 4 mA or 20 m

Page 16

dP: Number of decimal digits LO: Equivalent flow rate to 4 mA in the current loop UP: Equivalent flow rate to 20 mA in the current loop P/U: Pulse

Page 17

WARRANTY Tecfluid S.A. GUARANTEES ALL ITS PRODUCTS FOR A PERIOD OF 24 MONTHS, after consignment, against all defects in materials and workmanship. Thi

Page 18 - F(u/s)rateFlow f

3 7. MAINTENANCE …... 18 7.1. Fuse ……………………………..……………………………...

Page 19 - Hz 263.91002.639f

1 INTRODUCTION The XT5 converter is an electronic equipment that adapts to the Flomid and Flomat series electromagnetic flow sensors. The microprocess

Page 20 - WALL MOUNTING MODEL

2.1 Power supply connection Terminal AC Power supply DC Power supply Earth Earth N Neutral 0 V (-) L Phase 24 V (+) 5 It is import

Page 21

6 To configure the analog output type (active or passive) there is a slide switch situated just behind the terminal strip. For the passive mode the sw

Page 22

7 mA: Ammeter

Page 23 - SN: Serial number

2.3 Pulse output connection Terminal E Emitter. C Collector. 8 2.4 Connection examples The two usual ways to connect the alarm outputs are N

Page 24

9 PNP connection 2.5 Sensor connection When the electronics is mounted separate from the sensor, the interconnection is made through a cable gland. Th