M21 / AD
Transmitters HALLTEC VI
TH6, TH6H
For Series
R-MI-TH6 Rev.: 1 English version
Instructions Manual
Vue de la page 0
1 2 3 4 5 6 ... 11 12

Résumé du contenu

Page 1 - Instructions Manual

M21 / AD Transmitters HALLTEC VI TH6, TH6H For Series R-MI-TH6 Rev.: 1 English version Instructions Manual

Page 2

10 9 TROUBLESHOOTING Problem Probable cause Remedy The analog output gives always 0 mA Cables disconnected. Check the cable connection. The poin

Page 3

11 NOTES ……………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………

Page 4 - Flow rate

12 WARRANTY Tecfluid S.A. guarantees all the products for a period of 24 months from their sale, against all faulty materials, manufacturing or perfo

Page 6 - 18 to 36 VDC

3 TABLE OF CONTENTS 1 INTRODUCTION ... 4 2 MODELS ...

Page 7

4 1 INTRODUCTION The Halltec VI transmitter is an electronic position transducer with a microprocessor. The instrument uses the Hall effect to captur

Page 8

5 The connection is made in the terminal block. The positive terminal of the power supply is connected to the position + and the positive terminal of

Page 9

6 4 “WRITE PROTECT”. The instrument has a jumper that can be used to avoid changes in the configuration. When the jumper is connected the instrument

Page 10

7 7 TECHNICAL CHARACTERISTICS 7.1 Power supply 2 wire. Minimum voltage (TH6): 0.02 Z + 12 (Volt) (Z is the load in the current loop in Ohm). T

Page 11

8 7.4 Safety characteristics This material conforms with the following directives: 2004/108/EC Electromagnetic Compatibility. 2002/96/EC Waste elec

Page 12

9 8.3 Technical characteristics of the Exi version Maximum voltage: 30 VDC Maximum load in the 4-20 loop: 900  (at 30 VDC supply voltage)