DIMENSIONS
LC-30 LC-31
LC-30
DN PN D k g Lxno. b A B HB LE LI
25* 40 115 85 68 14x4 18 160 125
40 16 150 110 88 18x4 18 160 125
100* 16 220 180 158 18x8 20 160 125
150* 16 285 240 212 23x8 22 160 125
Related to the
individual measuring
range.
LC-31
R EC b A B HR LE LI
1 ½” 60 22 160 125 30 Related to
range
( * on request )
The wiring should be made according to the attached diagram.
When using inductive loads, such as relays or electro-valve coils, surge arresters should be
installed to protect the reed contacts.
With a dc supply, a diode should be used.
For an ac supply, an RC circuit can be used as shown, although a varistor (VDR) is better and is
easier to select the right value.
The VDR should have a breakdown voltage greater than 1.5 times the rms voltage.
The standard varistor ratings specify the rms working voltage for the varistor, for example a
S05K25 varistor will be for 25 V
rms
working and will have a breakdown voltage of 39 V at 1 mA.
WIRING